Technical data sheet ASOCRET-VK100 Cementitious under-grouting mortar, highly flowable
Material number
Contents
Unit of quantity
Packaging
Colour
206417001
25
KG
Bag
Grey
Product features Anchoring product in accordance with DIN EN 1504-6 Chloride-free Under-grouting heights from 20 - 100 mm
Advantages Highly flowable Cementitious Resistance to frost and thaw watertight Force-locking bond to concrete support layers
Areas of application For grouting voids For anchoring concrete kerbs, pre-cast concrete components, machine foundations, supports and crane runway rails For interior and exterior use
SCHOMBURG GmbH & Co. KG · Aquafinstr. 2–8 · D-32760 Detmold (Germany) · Tel. +49-5231-953-00 · Fax +49-5231- 953-333 · schomburg.com 1/3
30/01/2025
Technical data sheet ASOCRET-VK100 Technical Data Material properties Product components Base material Consistency Grain size max Bulk density of fresh mortar Discharge dimension Swelling dimension after 24 hrs. Compressive strength (24 hrs.) Compressive strength (28 days) Compressive strength (56 days) Compressive strength (90 days) Flexural strength (28 days) Flexural strength (56 days) Flexural strength (90 days) Classification of the reaction to fire in accordance with DIN EN 13501-1
1 component system Pre-blended dry mortar Flowable mortar < 4 mm approx. 2.3 kg/dm³ approx. 55 cm > 0.5 % approx. 50 N/mm² approx. 60 N/mm² approx. 70 N/mm² approx. 90 N/mm² approx. 9 N/mm² approx. 10 N/mm² approx. 11 N/mm² A1
Mixing Mixing time Water addition Water addition (percentage)
approx. 3 minutes Max. 3.5 l per 25 kg approx. 14 %
Application Substrate/application temperature Pot life Method of application, max. layer thickness per application step Consumption
approx. 5 - 30 °C approx. 60 minutes approx. 2 kg/m²
Processing equipment Aids/tools Stirrer (approx. 500-700 rpm) Suitable mixing paddle Trowel Flat trowel Forced paddle mixer
Machine application ASOCRET-VK100 can be mechanically applied. For precise information, see the additional Technical Information No. 43.
Preparing the substrate Requirement for substrate 1. 2. 3. 4. 5. 6.
Firm Grippy Load-bearing Free of adhesion inhibiting substances The quality of concrete must be at least C20/25. The tear-off strength of concrete substrates must not exceed an average of 1.5 N/mm² (lowest individual value 1.0 N/mm²).
SCHOMBURG GmbH & Co. KG · Aquafinstr. 2–8 · D-32760 Detmold (Germany) · Tel. +49-5231-953-00 · Fax +49-5231- 953-333 · schomburg.com 2/3
Technical data sheet ASOCRET-VK100 Preparing the surface 1. Remove loose / low strength layers from deeper damaged areas and build back to the solid core. 2. The formwork to be used must be secured in a stable manner and, if necessary, sealed. 3. Pre-moisten the dry substrate so that it is matt damp at the time of application.
Application Mixing 1. 2. 3. 4.
Put approx. 3.2 l of water into a clean mixing bucket and mix with 25 kg of the powder component to produce a homogeneous, lump-free mass. Pre-mix for approx. 3 minutes. Finally, add the remaining water quantity and mix sufficiently. The mixing time is ca. 3 minutes.
Application 1. Grouting / under grouting takes place from one side / corner only, so that the displaced air can escape more easily. Do not interrupt the grouting process. 2. For large-area grouting measures, start from the centre if possible. Funnels and/or appropriate tubing can be used to support this. 3. Carry out under-grouting measures continuously and without any interruption. Ensure a continuous flow of material.
Cleaning tools Clean tools thoroughly with water after use.
Storage conditions Storage Cool, dry, protected from sunlight. Min. 12 months in the original canister. Promptly use opened container.
Disposal Product residues can be disposed of in accordance with disposal code AVV 17 01 01.
Notes Protect surfaces that are not to be treated from the effects of ASOCRET-VK100! For each grouting measure that has to be carried out as under-grouting, the run-out dimension (as described in additional technical information no. 43) must be set. Exposed surfaces must be protected from wind and draughts. Premature evaporation of water must be avoided by covering with film. Lower temperatures and cold mixing water delay the strength development and reduce the flowability. Higher temperatures accelerate the strength development.
Observe applicable safety data sheet! GISCODE: ZP1 Explanations Conformity / Declaration / Verification
The rights of the buyer with regard to the quality of our materials are based on our terms and conditions of sale and delivery. Our technical advice team will be happy to advise you in the case of requirements that exceed the scope of the application described here. In order to be binding, a legally binding written confirmation is required. The product description does not release the user from a duty of care. Lay a test area in the event of uncertainty. This version becomes invalid in the event of a new version being issued.
SCHOMBURG GmbH & Co. KG · Aquafinstr. 2–8 · D-32760 Detmold (Germany) · Tel. +49-5231-953-00 · Fax +49-5231- 953-333 · schomburg.com 3/3